Duration: 21 minutes
Creation Date: October 22, 2024
Topics:
– Secondary line to line voltages not impacted by ground fault or unbalanced load
– Secondary line to neutural voltages not impacted by ground fault or unbalanced load
– Secondary line to ground voltages impacted by ground fault and not by unbalanced load
– Neutural to Ground voltages with ground fault
– Common Mode currents in connections to ground impacted by ground fault, not by unbalanced load
– Line currents into the wye load not impacted by ground fault and impacted by unbalanced loads
– Line current on faulted phase of secondary moderately higher than other phases - no fault protection tripping
– Unbalanced loads results in current in the neutral conductor
– Ground Fault Current limited by HRG
Video Copyright 2024 by Norbert Doerry and John Amy – licensed via CC BY 4.0
Presentation (PowerPoint) Copyright 2024 by Norbert Doerry and John Amy – licensed via CC BY 4.0
LTSpice Model Copyright 2024 by Norbert Doerry and John Amy – licensed via CC BY 4.0(C) Copyright 2024 Norbert Doerry
This work by Norbert Doerry is licensed under CC BY 4.0