Marine Electrical Power Systems:
Videos:
Wye–Wye Transformer – 4 wire – solidly system – unbalanced load and ground fault

Last Update: November 7, 2024

Duration: 21 minutes
Creation Date: November 4, 2024

Topics:
– Secondary line to line voltages not impacted by ground fault or unbalanced load
– Secondary line to neutural voltages not impacted by ground fault or unbalanced load
– Secondary line to ground voltages impacted by ground fault and slightly impacted by unbalanced load
– Neutural to Ground voltages with ground fault and unbalanced load
– Common Mode currents in connections to ground impacted by ground fault, and somewhat by unbalanced load
– Line currents into the wye load not impacted by ground fault and impacted by unbalanced loads
– Line current on faulted phase of secondary moderately higher than other phases - no fault protection tripping
– Ground Fault and Unbalanced loads results in current in the neutral conductor
– Ground Fault Current limited

Video Copyright 2024 by Norbert Doerry and John Amy – licensed via CC BY 4.0

Presentation (PowerPoint) Copyright 2024 by Norbert Doerry and John Amy – licensed via CC BY 4.0

LTSpice Model Copyright 2024 by Norbert Doerry and John Amy – licensed via CC BY 4.0
(delete .txt file extension)